Design and Signal Extraction Technology of Wide-band Composite Sensors for High Voltage Transmission Equipment
DOI:
https://doi.org/10.62051/vh57ee32Keywords:
Partial discharge; Ultra high frequency; Bandwidth; High voltage transmission equipment.Abstract
Renewable resources and power electronic transformation are important trends in power grid conversion now. It is very important to ensure the normal operation of high-voltage transmission equipment, and online monitoring must be selected. The early characteristic of insulation degradation is partial discharge. Partial discharge (PD) has an extremely wide spectrum, because it is from power frequency to ultra-high frequency; therefore, the bandwidth and sensitivity of the sensor are very important. Due to its own physical limitations, traditional single-model sensors exhibit insufficient bandwidth, resulting in the problem of frequency domain and time domain truncation. This work investigates micro multi-model composite sensors. Coupling inductance and capacitance in the same sensor to achieve complementation and mutual verification. This work couples inductance and capacitance within the same sensor to achieve complementation and mutual verification. Because composite sensors will produce a lot of parasitic resonances and channel impedance differences, it is necessary to add broadband impedance matching, low-noise amplification and two-stage filters. The scheme can effectively restore the PD pulse waveform of the full frequency band, thereby enabling the evaluation of the insulation condition of high-voltage equipment through these data.
Downloads
References
[1] Chai H., Phung B.T., Mitchell S. Application of UHF sensors in power system equipment for partial discharge detection: a review. Sensors, 2019, 19(5): 1029.
[2] Zhang X., Pang B., Liu Y., Liu S., Xu P., Li Y., et al. Review of partial-discharge detection and localization for XLPE power cables. Energies, 2021, 14(22): 7692
[3] Ardila-Rey J.A, Rojas-Moreno M.V., Martínez-Tarifa J.M., Robles G. Inductive sensor performance in partial discharges and noise separation by means of spectral power ratios. Sensors, 2014, 14(2): 3408–3427.
[4] Uwiringiyimana J.P., Khayam U., Suwarno., Montanari G.C. Planar rectangular microstrip antenna for partial discharge detection: experimental validation on oil-filled transformer tank. IEEE Access, 2024, 12: 133199-133208.
[5] Hu X., Siew W.H., Judd M.D., Peng X. Transfer function characterization for HFCTs used in partial-discharge detection. IEEE Transactions on Dielectrics and Electrical Insulation, 2017, 24: 1088-1096.
[6] Rodrigo A., Llovera P., Fuster V., Quijano A. High performance broadband capacitive coupler for partial discharge cable tests. IEEE Trans. Dielectr. Electr. Insul., 2013, 20(2): 479–487.
[7] Wen H., Abu Talip M.S., Othman M., et al. Advanced signal processing methods for partial discharge analysis: a review. Sensors, 2025, 25(23):7318.
[8] Jia J., Fu H., Wang B., Li Y., Yu Y., Cao Y., Jiang D. Acoustic-electrical joint localization method of partial discharge in power transformer considering multi-path propagation impact. Front. Energy Res., 2022, 10: 851299.
[9] Chen B., Hu Y., Wu L. Deep learning-based multisource partial discharge pattern recognition integrated with auxiliary prior localization information. IEEE Trans. Dielectr. Electr. Insul., 2025, 32(6): 3209–3217.
[10] Alvarez F., Garnacho F., Ortego J., Sánchez-Urán M.A. Application of HFCT and UHF sensors in on-line partial discharge measurements for insulation diagnosis of high-voltage equipment. Sensors, 2015, 15(4): 7360–7387.
Downloads
Published
Issue
Section
License
Copyright (c) 2026 Transactions on Computer Science and Intelligent Systems Research

This work is licensed under a Creative Commons Attribution-NonCommercial 4.0 International License.